|
Toll free 888 887-5625 Cell 352 318-5625 or Email mail@greenskyadventures.com
|
|
A previous production series of carb bodies was cast to accept the HAC but not drilled or tapped. People with modest machinist abilities, can modify this series carb body in the field. Click HERE for images
|
*Plumbing Revision was implemented April of 2004. Vent Tee's are eliminated and Carb Vent lines connect directly to the HAC Chamber. See HAC Plumbing 2004 for additional details |
Please note, the following information is provided as a supplement to the normal, simple installation process. Green Sky Adventures, Inc. ships HAC kits calibrated, and ready to install. Simply change the appropriate main jet, and that's it. However, if there is ever a reason to doubt the function of the HAC, or if one wishes to perform a periodic inspection, The information below is "must have"
Early HAC chambers were shipped with instruction to verify calibration upon initial installation and annually. Within a few years, field experience indicated calibration from "factory" settings does not change (unless a failure occurs). The previously removable screw 2, above, in current production, is sealed over. Calibration can still be checked, but adjustment cannot be made without removing the sealing material and screw. Variation from proper calibration can alternatively be corrected by custom jetting change. For that reason you may see conflicting recommendations for jetting. |
Calibration check requires:
Density Altitude information and the corresponding HAC metering pin position information. (see table, below) Because the metering pin moves with changes in Density Altitude, it's position is referenced to that and can be measured. Metering pin position measurement is taken by measuring the space between the top of the metering pin and the end of the vacuum connection pipe. (Dimension E) Example at right: After determining Density Altitude and the corresponding Dimension E, a wooden insert was cut to that length and dropped into the vacuum connection pipe. It should be flush with the top. Allowable variance is plus or minus .5 mm. If the metering pin is out too far, (dimension E too small) the sealed screw must be loosened to bleed pressure from the sealed side of the chamber. |
If the metering pin isn't out far enough (dimension E too large), loosen sealing screw, and apply slight suction to the vacuum connection pipe with the remaining tubes blocked off. Close the sealing screw. At this point, the metering pin should be almost to the top (Dimension E = 0) then, just as above, loosen the (previously) sealed screw, gradually, bleeding out pressure till the pin goes back down and dimension E is correct. |
| Density Altitude is a calculation, based on Altitude, Temperature,
Atmospheric Pressure (altimeter setting), and Dew Point. You can get the
"current weather conditions" for your area. in about 30 seconds, from the National Weather service. You will get data as shown at left. Armed with that data, click on the Density Altitude Calculator and by inputting the data as in the example below, you will find the DA just as quickly. (you must also know the altitude of the reporting station) |
http://weather.noaa.gov/weather/ccus.html http://wahiduddin.net/calc/calc_da.htm |
Dimension E (mm) / Density Altitude (ft)
|
Density Altitude Sample We worked a sample on Mar 10, 2003 out of Gainesville Florida. Above is the view of the National Weather Service input, and the the DA calculator results. As luck would have it, on this morning, the DA calculated out to 0 feet msl.Jetting changes are required. There are a variety of conflicting data in published charts. In setting up an engine for HAC operation, a technician must take into consideration the default is generally towards rich, meaning the HAC is continuously leaning the mixture. Initial jet selection therefore is larger. Below, is a recommendation which may be used as a starting point. This may not ultimately be the final combination of jets for a particular installation. As always, careful monitoring of EGT is mandatory, especially during set up process.
- Jan 2003: Randomly checking calibration, our observation indicated a larger main jet requirement than certain published suggestions. The chart below is a modified Bing chart. These are the the jets provided with HAC kits shipped between November 2002 and Mar 2003
![]() |
|
![]()
Measuring Deflection
|
Important Clarification and Jetting Note: Standard 503 Dual Carb without air intake silencer, and without HAC was changed around 1992. Old jetting used an 8L2 Jet Needle in Position 1 and a 2.74 Needle Jet. On that vintage, when HAC was added, the only jet change was the main jet. It went from 158 to 185. In the early nineties, the standard mid range jetting was changed to the current 11K2 Needle in position 2 and a 2.70 Needle Jet. This setup yielded about the same mixture, but would allow for Needle Clip adjustments, as required. (notice the early version had the clip at extreme top position leaving no available adjustment) When the jetting change was made, that change was never reflected in the 503 DC HAC jetting chart. Consequently, those who changed to the HAC setup on late engines have been reverting to the older version mid range jetting for no valid reason. Initially, HAC installation should only require Main Jet changes. Close monitoring of EGTs may indicate other changes, but only on a case by case basis. If other mid range jetting is effectively in use, initial change of the Main Jet, only, is the general recommendation. |
![]() ![]() |
3. Slide or Piston
4. Jet Needle Clip
5. Jet Needle O-ring
6. Spring Cup
7. Slide Spring
8. Carb Top O-ring
9. Carb Top
10. Carb Top Screws
11. M6 Jam Nut
12. Cable Housing Adjuster
13. Cable Grommet14. Mixing Tube
15. Sieve Sleeve
16. Float Needle
17. Float Needle Clip
18. Floats
20. Float Hinge
21. Float Chamber Gasket
38. Idler Jet
39. Needle Jet
40. Main Jet
Float Bracket